Electrical · in the TradeTools app
Voltage Drop Calculator
AC voltage drop on a branch circuit or feeder from the Table 9 conductor impedance, the voltage left at the load, and the minimum conductor size that keeps the drop within the recommended 3 %.
NEC Ch. 9 Table 9Calculate it now
That's today's free web calculations. Keep going in the app: 15 free calculations, 5 more for a short ad, or no limit with Pro — a one-time purchase, no subscription. Or come back tomorrow.
Continue in the appInputs changed — press Calculate.
Worked example above. Change the inputs and press Calculate.
- Voltage drop
- —
- Voltage at the load
- —
- Effective impedance
- —
- Smallest size within 3%
- —
On the job, keep it. The app saves this run, exports it as a PDF with the NEC table cited for the inspector, adds the result to a quote, and works with no signal.
Get TradeTools on Google PlayWorked example
200 ft to the shop on 10 AWG at 20 A — how much do you lose?
| Voltage / phase | 240 V, single-phase |
|---|---|
| Conductor | 10 AWG copper |
| Raceway | PVC |
| One-way length | 200 ft |
| Load | 20 A |
| Power factor | 0.85 |
| Voltage drop | 8.37 V |
|---|---|
| Percent | 3.49 % — above the recommended 3 % |
| Voltage at the load | 231.6 V |
| Effective impedance | 1.046 Ω/kft (NEC Ch. 9 Table 9) |
| Smallest size within 3 % | 8 AWG |
Impedance is computed from Table 9's resistance and reactance for uncoated copper in PVC at 0.85 power factor: 1.2 × 0.85 + 0.050 × 0.527 = 1.046 Ω per 1000 ft. Two conductors, 200 ft, 20 A: 2 × 200 × 20 × 1.046 / 1000 = 8.37 V, or 3.49 % of 240 V. 8 AWG brings it under 3 %.
How it's calculated
The table behind the number
The app takes the conductor's AC resistance and inductive reactance from NEC Chapter 9 Table 9 for the raceway material, combines them at the power factor you enter (R·cos θ + X·sin θ, Table 9 Note 2), and computes the drop for single-phase (2 × length) or three-phase (√3 × length) circuits. It reports the drop in volts and percent, the voltage at the load, and the smallest conductor that stays under the 3 % that 210.19 and 215.2(A)(2) recommend in their informational notes.
- NEC 2023 Chapter 9, Table 9AC resistance and reactance for 600 V conductors, by raceway material
- NEC 2023 210.19, Informational Note3 % branch-circuit drop — a recommendation, not a requirement (90.5(C))
- NEC 2023 215.2(A)(2), Informational Note No. 25 % combined feeder and branch-circuit drop — recommendation
Questions
Before you trust the number
Is 3 % voltage drop a code requirement?
No. The 3 % and 5 % figures live in informational notes, which 90.5(C) defines as explanatory material. Your AHJ or the job specification may make them mandatory; the NEC itself does not.
Why does the printed 0.85 PF column give a different answer?
Table 9 also prints an 'effective Z at 0.85 PF' column rounded to two digits; the app computes the impedance from the R and X columns for the power factor you enter, which is what the table's Note 2 describes. The conclusion — over 3 %, 8 AWG gets under — is the same.
