Equipment Circuit Calculator

The minimum circuit ampacity, the overcurrent protection and the disconnect rating for a single motor-compressor — an air conditioner or heat pump condenser — from its rated-load and fan currents. An optional BCSC field takes the branch-circuit selection current when the nameplate marks one: if it is greater than RLA, it replaces RLA for the wire, the breaker and the disconnect (NEC 2023/2026 440.6(A) Exc. 1, 440.32). The equipment's own nameplate governs whenever it marks a maximum.

NEC 2023/2026 440.32 · 440.22 · 440.12
Get it on Google Play

Calculate it now

Inputs changed — press Calculate.

Worked example above. Change the inputs and press Calculate.

—

On the job, keep it. The app saves this run, exports it as a PDF, and works with no signal.

Get TradeTools on Google Play

Worked example

A 2.5–3 ton condenser on an old 40 A breaker — keep the breaker, or size it fresh?

Inputs
EquipmentSplit A/C
Supply230V 1-Phase
Compressor RLA16.0 A
Fan motor FLA1.5 A
What the app shows
Minimum circuit ampacity21.5 A
Maximum overcurrent protection25 A — 175% of the largest motor plus the other loads, rounded down to a standard size (NEC 440.22(B)(1))
Maximum at 225%, if 175% can't start the motor35 A — never above 225%, rounded down (NEC 440.22)
Disconnect, at least≥ 20.2 A — 115% of all currents, NEC 440.12(B)(2); ampere rating only, check the horsepower rating too
Breaker25 A — use the nameplate's own Max Fuse or Max Breaker size instead, when the equipment has one marked (NEC 440.22(C), 110.3(B))
Conductor10 AWG
Total running load17.5 A

MCA is 125% of the largest motor's current plus the rest of the load (NEC 440.32-440.33): 1.25 × 16.0 + 1.5 = 21.5 A. With a fan on the same circuit, branch-circuit protection may go up to 175% of the largest motor plus the rest (NEC 440.22(B)(1)) — 1.75 × 16.0 + 1.5 = 29.5 A, rounded down to the standard 25 A size — or up to 225% if 175% can't start the compressor: 2.25 × 16.0 + 1.5 = 37.5 A, rounded down to 35 A. The disconnect needs an ampere rating of at least 115% of all the currents added (NEC 440.12(B)(2)): 1.15 × 17.5 = 20.125 A, shown rounded up as ≥ 20.2 A; its horsepower rating is a separate check. Either breaker ceiling is below the old 40 A breaker already on the wall, so replacing it is reasonable either way — but the equipment's own nameplate, once marked, is what actually governs (NEC 440.22(C), 110.3(B)), not either calculated ceiling.

How it's calculated

The table behind the number

MCA (minimum circuit ampacity) is 125% of the largest motor-compressor's current, plus the rest of the load (NEC 440.32-440.33). When the nameplate marks a BCSC (branch-circuit selection current) greater than RLA, the app uses BCSC instead of RLA for the MCA, the breaker and the disconnect (NEC 2023/2026 440.6(A) Exc. 1). Branch-circuit protection: a compressor alone may have up to 175% of its RLA or BCSC, and when that is not a standard size, the next higher standard size (440.22(A) Exc. 1); with a fan or other loads, 175% of the largest motor plus the rest, rounded down to a standard size (440.22(B)(1)). A second reading at 225% covers a compressor that can't start at 175% — never above 225%, rounded down in both cases (440.22(A) Exc. 2). The disconnect row is the minimum ampere rating: 115% of the compressor current alone (440.12(A)(1)) or of all the currents added (440.12(B)(2)) — check its horsepower rating too. The Breaker row repeats the 175% figure, with a note that a marked nameplate maximum takes over once the manufacturer states one (NEC 440.22(C); the equipment must be installed per its own listing or labeling instructions, NEC 2023 110.3(B)).

  • NEC 440.32–440.33Minimum circuit ampacity: 125% of the largest motor-compressor's current (RLA, or BCSC when greater), plus the rest of the load in the circuit
  • NEC 2023/2026 440.6(A) Exc. 1Where a BCSC is marked, it is used instead of RLA to size the conductors, the disconnect and the short-circuit protection
  • NEC 440.12(A)(1)Disconnect for a motor-compressor: ampere rating at least 115% of RLA or BCSC, whichever is greater
  • NEC 440.12(B)(2)Disconnect for a compressor with other loads: ampere rating at least 115% of all the currents added
  • NEC 440.22(A) Exc. 1A compressor alone: up to 175% of RLA or BCSC; when that is not a standard size, the next higher standard size is allowed
  • NEC 440.22(A) Exc. 2Where 175% can't start the motor, protection may be raised, but never above 225%
  • NEC 440.22(B)(1)A compressor with other loads: the 175% value of the largest compressor plus the other loads
  • NEC 440.22(C)Once the equipment's nameplate marks a maximum overcurrent-protective-device size, protection can't exceed that marked value
  • NEC 2023 110.3(B)Listed or labeled equipment must be installed and used according to its own listing or labeling instructions

Questions

Before you trust the number

What's the difference between MCA and MOCP?

MCA (minimum circuit ampacity) sizes the conductor — 125% of the largest motor plus the rest of the load. MOCP (maximum overcurrent protection) sizes the breaker or fuse ceiling — up to 175% of the largest motor-compressor's current plus the rest of the load, or up to 225% if the compressor needs it to start. They're two different numbers for two different parts of the circuit.

What is BCSC, and when does it replace RLA?

BCSC (branch-circuit selection current) is printed on some compressor or equipment nameplates next to RLA. When it is marked and greater than RLA, it replaces RLA for the wire, the breaker and the disconnect (NEC 2023/2026 440.6(A) Exc. 1, 440.32). Leave the field empty if the nameplate doesn't mark one — the app then uses RLA, and the card says which one it used.

Why does the card show a 225% figure at all, if the breaker is already sized at 175%?

Because 175% is only the usual ceiling — NEC 440.22(A) Exc. 2 allows up to 225% where 175% can't carry the compressor's starting current, never above 225% and rounded down. The app shows both so the full range the code allows is visible.

Why can a compressor alone get a bigger breaker than 175%?

For a compressor alone, NEC 440.22(A) Exc. 1 allows the next higher standard size when 175% falls between sizes: RLA 16.0 A × 1.75 = 28 A, so 30 A. With a fan on the same circuit (440.22(B)(1)), the app rounds the sum down instead — that is why this page's example shows 25 A.

What does the disconnect row mean?

It is the minimum ampere rating of the disconnecting means: 115% of the compressor current alone (NEC 440.12(A)(1)) or of all the currents added when there are other loads (440.12(B)(2)). It is shown rounded up, so it never reads less than required. The horsepower rating of the disconnect is a separate check the app does not do.

If the equipment's nameplate marks a maximum, does that override the calculation?

Yes. Once a manufacturer marks a maximum overcurrent-protective-device size on the nameplate, NEC 440.22(C) caps protection at that value — the calculated 175%/225% figures apply only when no nameplate maximum is marked.

Is 25 A or 35 A the 'right' breaker for this circuit?

Neither is a target — both are ceilings: 25 A at 175% with the fan (440.22(B)(1)), 35 A at 225% (440.22(A) Exc. 2). The old 40 A breaker is above both, so it gets replaced either way; a marked nameplate maximum sets the size (440.22(C), 110.3(B)).